With the Extech 380396, measure insulation resistance to 60 GΩ with test voltages of 500 V, 1000 V, 2500 V, and 5000 V. It features several measurements including polarization index (PI), dielectric absorption ratio (DAR), and AC/DC voltage to 600 V with a min/max function. It also has peak and relative functions, as well as a 1 to 15 minute timer function for IR measurements. Comes with test leads, eight C batteries, 220 V AC adaptor, heavy duty carrying case, and user manual.
Added to cart
Specifications
General Specifications
- AC Voltage
- 0 to 600V
- AC Voltage Basic Accuracy
- ±1% of reading
- Continuity
- 50Ω
- DC Voltage
- 0 to 600V
- DC Voltage Basic Accuracy
- ±1% of reading
- Insulation Resistance
- 6MΩ, 60MΩ, 600MΩ, 6GΩ, 60GΩ
- Insulation Resistance Basic Accuracy
- ±2.5% of reading
- Insulation Test Voltage
- 500V, 1000V, 2500V, 5000V
- Resistance
- 0 to 600Ω
Additional Details
- Certifications
- CE
- Dimensions
- 7.8 × 5.8 × 3.4" (198 × 148 × 86mm)
- Display
- Backlit segment LCD with bargraph
- Power
- 8 × C (1.5V) batteries, 220V AC adaptor
- Safety Category
- CAT IV-600V
- Warranty
- 2 years
- Weight
- 3.2lb (1438g)
Related Documents
Export Restrictions
Export Restrictions
The information contained in this page pertains to products that may be subject to the International Traffic in Arms Regulations (ITAR) (22 C.F.R. Sections 120-130) or the Export Administration Regulations (EAR) (15 C.F.R. Sections 730-774) depending upon specifications for the final product; jurisdiction and classification will be provided upon request.